Breaker Opened
Grid Voltage
Grid Frequency
Mode Island Mode
Primary Source BESS
Relay Control
EMS Control
Auto Disconnection Logic (Anti-Islanding): Relay Control
Relay Control
CodeAuto Trip CriteriaCurrent Status
A1Grid voltage/frequency exceeds limitOV>110% · UV<85% · OF>50.5Hz · UF<49.5HzNot Triggered
A2Grid power outage (no voltage)V<5V sustained >100msNot Triggered
A3ROCOF ≥ thresholdRate-of-change-of-frequency > 1.0 Hz/sNot Triggered
A4Trip action completed52b contact confirmed — breaker mechanically openStandby
A5Trip signal reported to EMSEvent logged · UI alert triggeredStandby
A6Island mode startup permittedBESS grid-forming · SOC · load coordination verifiedNot Allowed
Anti-Reverse Power Detection: Enabled
Set mode: Enabled / Disable
CodeDescriptionStatusAction Suggestion
R1Reverse power detected at POINot TriggeredNo action required
R2PV/BESS output power = 0Required before reconnection attemptNot SatisfiedMaintain current state
R3EMS enabled "Zero Export" strategyEnabledReverse power protection active
POI Active Power+84.1 kW
Reverse Power Limit10.0 kW
BESS Output+19.7 kW
Grid Reconnection (Breaker Close) Control Logic
Conditions met: 2/5
EMS Control active — Operator can authorize breaker close. All C1–C5 prerequisites must be met before Close is permitted.
C1
C2
C3
C4
C5
CLOSE
ΔV
4.0 V
Δf
0.24 Hz
Δθ
20.3°
ΔV limit
≤ 2.0 V
Δf limit
≤ 0.05 Hz
Δθ limit
≤ 5°
NOT SYNCHRONIZED
Code Prerequisite Status Description
C1 Stable grid voltage, frequency, phase ≥ 60sV:220–240V · f:49.8–50.2Hz · 60s window Satisfied Grid has been stable over 60s
C2 Power flow is "inflow" or "zero export"POI flow must not be export before reconnect Satisfied No reverse power
C3 PV/BESS is stopped or in standbyAll DER output must be zero — avoids power surge Not Satisfied BESS is still running
C4 EMS authorized breaker closeSolely authorized by EMS via UI interlock engine Not Allowed
C5 Phase/frequency sync completeΔf<0.05Hz · ΔV<2V · Δθ<5° confirmed Not synchronized Parameters not matched
C3
Assets Not Stopped — Primary Blocking Condition
BESS is actively discharging. Output power > 0 kW.
Required Action
Execute Force Stop BESS, confirm output = 0 kW before proceeding.
⚑ C4 (EMS Auth) and C5 (Phase Sync) cannot be evaluated until C3 is cleared.
Operator Guidance — Reconnection Sequence
Action Required
1
Verify grid stability ≥ 60s (C1)
Grid stable for 60s confirmed ✓
✓ COMPLETED
2
Confirm zero export / inflow only at POI (C2)
No reverse power ✓
✓ COMPLETED
3
Stop BESS & PV — wait until output = 0 kW (C3)
Use Force Stop BESS + Force Stop PV in control bar
⚠ ACTION
4
Await EMS authorization for breaker close (C4)
🔒 Requires C3 satisfied first
LOCKED
5
Phase sync complete — ΔV<2V · Δf<0.05Hz · Δθ<5° (C5)
🔒 Requires C3 + C4 first
LOCKED
Breaker
Force Stop
Grid-Tie
RECONNECT BLOCKED — C3 Not Satisfied
SYS LOG
Confirm
Please confirm.
Grid Reconnection Successful
The main breaker has been closed. System is now operating in Grid-Tied mode.
Timestamp
OperatorAdmin
System StateGRID_TIED
Breaker 52aCLOSED (TRUE)
Breaker 52bOPEN (FALSE)